|
| |
 |
|
|
Distance Learning Steam Basics Answers
|
Session 1
(Thermodynamics of Steam), Self Quiz Answers
- The
saturation temperature of 100 PSIG steam is 338 deg-F.
- False.
Steam quality refers to the % of dry steam in a steam/water droplet
mix.
- From
Table 1, the 5 Flash is 11.7%, so flash quantity is 5,000 #/HR X 0.117 = 585
#/HR
-
Per Equation 1, Q = 1,000 #/HR X (hg @ 5 PSIG
– hf @ 160 deg-F)
where hg @ 5 PSIG = 1156 BTU/#
and hf @ 160 deg-F = 1.0 X (160 – 32) = 128 BTU/#
So Q = 1,000 X (1156 – 128) = 1,028,000 BTUH
- Per
the formula for “Heat Exchanger, Fluid, GPM Known” on Page 15:
BTUH = 500 X GPM X SH X SG X
ΔT
= 500 X 40 X
1.10 X 0.88 X (140 – 70) = 1,355,200 BTUH
Hfg
of 2 PSIG steam = 965
#/HR of steam
= 1,355,200/965 = 1,404 #/HR
Mind Teaser A: Per Table 2, the steam is leaving Phil’s PRV at 311
deg-F, considerably above the 230 deg-F rating of the O-Rings.
Farron, on the other hand is using plain old saturated steam at 5
PSIG/228 degrees. This is close to
the rating but obviously the manufacturer has built in a little safety so his
valves last.
Mind Teaser B: The geyser if
from flash steam, not a leaky trap.
Mind Teaser C: A light loads,
the control valve knocks the pressure of the steam down.
Because condensing takes place at the saturation temperature
corresponding to the saturation pressure in the heat exchanger, at light loads
there is insignificant flash. When
the load ramps up, the valve opens so that the steam enters the heat exchanger
at a much higher pressure, which, per Table 1 results in more flash steam.
The traps are fine.
___________________________________________________________________
Session II, Steam Trap Basics
1. Inverted Bucket 2. F & T 3. Small
hole in top of bucket
4. 2:1 at 1/2 PSIG, F & T 5. 0.43
#/ft. 6. Thermostatic bellows
7. Thermodynamic and Inverted Bucket
8. Accumulation of condensate in mains results in steam hammer, which is
noisy and can damage equipment.
9. 0.5" or 0.75" #1031-125 IB Watson McDaniel inverted bucket trap
Session
III, Piping Details
1. D 2. Condensate Stall 3. It is generally
not necessary to install vents on heat transfer equipment. Air is heavier
than steam and will usually eventually be vented to the condensate system
through the trap BUT during start up the heat transfer system sees only air (it
is pushed ahead of the steam) and lots of it. To avoid extended start up
times, separate air vents have a role because they have a greater venting
capacity than traps.
4. This is a good application for both. The vacuum breaker ensures that
the collapsing steam in the heat exchanger will not cause a vacuum; without the
air vent, the frequent start ups could be irritatingly slow and probably quite
costly in terms of lost production time.
5. The modulating valve is likely reducing steam pressure to a vacuum.
Make sure there is a vacuum breaker to ensure that a vacuum is not holding back
condensate. The 4" drip leg only results in a static head of 0.14 PSI
so the trap is undersized. A larger trap might work but a longer drip leg
might be required, even if it means chopping a hole in the floor or raising the
unit.
6. The system has air in it. Vent the air.
7. Double traps, an overflow trap in an extended (longer) drip leg.
8. Using one control valve is should be fine. Trap the three coils
separately, however.
9. Condensate is hanging up and surrounding the bottom tubes. Steam
bubbles are forming in the condensate next to the tubes and are imploding,
causing the "ball peen hammer effect." Things to check for to
ensure that condensate drains: Properly sized trap, proper drip leg, condensate
stall (is there excessive condensate lift?), presence of a vacuum
breaker. Also check for excessive pressure in return main and heat
exchanger pitch (is it pitched toward toward condensate outlet?
NOTE: Any and every question is welcomed.
Best Regards,
Bill Armstrong
Fluid Handling Inc.
Phone: 414-358-2646 Fax: 414-358-8388
E-Mail: billarm@fluidh.com
|